The Problem
200,000 sq ft warehouse had 5 PSI/hour pressure loss in fire loop. Discharge for testing would trigger a $50K recharge.
Detection Method
Acoustic correlation + pressure decay testing on the buried fire loop. Identified flange joint leak 60m from pump house.
Results
2m patch at exact location. Gasket replaced. No sprinkler discharge needed. Insurer accepted as compliance.